Self-limiting Parallel Heating Cable HSB
07-5803-...A
Features
- Steam cleaning possible
- Self-limiting
- Can be used in explosive atmospheres without temperature limiter (subject to
Certificates















Ex protection type


Ambient temperature
Cut-in heating cable +120 °C
Cut-off heating cable +190 °C
Minimum installation temperature -60 °C
Minimum cut-in temperature -60 °C
Description
A temperature-dependant resistive element between two parallel copper conductors regulates and limits the heat output of the heating cable. This output regulation is carried out automatically along the entire length of the heating cable according to the prevailing ambient temperature. As the ambient temperature rises, the heat output of the cable is reduced. This self-limiting property prevents overheating even when the cable are overlapped. A temperature limiter is not required (not even in explosion hazard zones).Thanks to the parallel power supply the heating cable can be cut to any required length. This feature considerably simplifies project planning and installation. The heating cable is cut and terminated in accordance with the local requirements directly on the construction site. In cases where the cable may become damaged, it is not necessary to replace the whole circuit but only the affected part. BARTEC-HEAT HSB is available in different versions and with different power outputs.
Technical data (extract)
(Click here for more information)Dimensions | with protective braid and protective outer jacket of fluoropolymer: 10.2 x 4.8 mm Min. bending radius: 25 mm |
Length of heating circuit | see data sheet |
Storage temperature | min. -60 ?C |
Heat output | 10 W/m, 15 W/m, 25 W/m, 30 W/m, 45 W/m, 60 W/m (at +10 ?C) |
Voltage | AC 208 V up to 254 V AC 110 V up to 120 V |
Resistance | Protective braid: < 18.2 Ω/km |